+MONITOR rack@localhost 1 admin baller primary
+
+FINALDELAY 180
+
+# Network UPS Tools: example upsmon configuration
+#
+# This file contains passwords, so keep it secure.
+
+# --------------------------------------------------------------------------
+# RUN_AS_USER <userid>
+#
+# By default, upsmon splits into two processes. One stays as root and
+# waits to run the SHUTDOWNCMD. The other one switches to another userid
+# and does everything else.
+#
+# The default unprivileged user is set at compile-time with the option
+# 'configure --with-user=...'
+#
+# You can override it with '-u <user>' when starting upsmon, or just
+# define it here for convenience.
+#
+# Note: if you plan to use the reload feature, this file (upsmon.conf)
+# must be readable by this user! Since it contains passwords, DO NOT
+# make it world-readable. Also, do not make it writable by the upsmon
+# user, since it creates an opportunity for an attack by changing the
+# SHUTDOWNCMD to something malicious.
+#
+# For best results, you should create a new normal user like "nutmon",
+# and make it a member of a "nut" group or similar. Then specify it
+# here and grant read access to the upsmon.conf for that group.
+#
+# This user should not have write access to upsmon.conf.
+#
+# RUN_AS_USER nut
+
+# --------------------------------------------------------------------------
+# MONITOR <system> <powervalue> <username> <password> ("primary"|"secondary")
+#
+# List systems you want to monitor. Not all of these may supply power
+# to the system running upsmon, but if you want to watch it, it has to
+# be in this section.
+#
+# You must have at least one of these declared.
+#
+# <system> is a UPS identifier in the form <upsname>@<hostname>[:<port>]
+# like ups@localhost, su700@mybox, etc.
+#
+# Examples:
+#
+# - "su700@mybox" means a UPS called "su700" on a system called "mybox"
+#
+# - "fenton@bigbox:5678" is a UPS called "fenton" on a system called
+# "bigbox" which runs upsd on port "5678".
+#
+# The UPS names like "su700" and "fenton" are set in your ups.conf
+# in [brackets] which identify a section for a particular driver.
+#
+# If the ups.conf on host "doghouse" has a section called "snoopy", the
+# identifier for it would be "snoopy@doghouse".
+#
+# <powervalue> is an integer - the number of power supplies that this UPS
+# feeds on this system. Most personal computers only have one power supply,
+# so this value is normally set to 1, while most modern servers have at least
+# two. You need a pretty big or special box to have any other value here.
+#
+# You can also set this to 0 for a system that doesn't take any power
+# from the MONITORed supply, which you still want to monitor (e.g. for an
+# administrative workstation fed from a different circuit than the datacenter
+# servers it monitors). Use <powervalue> if 0 when you want to hear about
+# changes for a given UPS without shutting down when it goes critical.
+#
+# <username> and <password> must match an entry in that system's
+# upsd.users. If your username is "upsmon" and your password is
+# "blah", the upsd.users would look like this:
+#
+# [upsmon]
+# password = blah
+# upsmon primary # (or secondary)
+#
+# "primary" means this system will shutdown last, allowing the secondary
+# systems time to shutdown first.
+#
+# "secondary" means this system shuts down immediately when power goes
+# critical and less than MINSUPPLIES power sources have reliable input feeds.
+#
+# The general assumption is that the "primary" system is the one with direct
+# connection to an UPS (such as serial or USB cable), so the primary system
+# runs the NUT driver and 'upsd' server locally and can manage the device,
+# and it would often tell the UPS to completely power itself off as a step
+# in power-race avoidance (see POWERDOWNFLAG for details).
+#
+# Also, since the primary system stays up the longest, it suffers higher risks
+# of ungraceful shutdown if the estimation of remaining runtime (or of the
+# time it takes to shut down this system) was guessed wrong. By consequence,
+# the "secondary" systems typically monitor the power environment state
+# through the 'upsd' processes running on the remote (often "primary") systems
+# and do not directly interact with an UPS (no local NUT drivers are running
+# on the secondary systems). As such, secondaries typically shut down as
+# soon as there is a sufficiently long power outage, or a low-battery alert
+# from the UPS, or a loss of connection to the primary while the power was
+# last known to be missing.
+#
+# This assumption and configuration can also make sense for networked UPSes,
+# where a rack full of servers might overload the communications capacity
+# of the networked management card on the UPS - in this case you might either
+# reduce the 'snmp-ups' or 'netxml-ups' driver polling rate, or dedicate a
+# "primary" server and set up the rest as "secondary" systems.
+#
+# In case of such large setups as mentioned above, beware also that shutdown
+# times of the rack done all at once can substantially differ from smaller
+# scale experiments with single-server shutdowns, since systems can compete
+# for shared storage and other limited resources as they go down (and also
+# not everyone may safely shut down simultaneously - e.g. a NAS or DB server
+# would better go down after all its clients). You would be well served by
+# higher-end UPSes with manageable thresholds to declare a critical state.
+#
+# Examples:
+#
+# MONITOR myups@bigserver 1 upswired blah primary
+# MONITOR su700@server.example.com 1 upsmon secretpass secondary
+# MONITOR myups@localhost 1 upsmon pass primary # (or secondary)
+
+# --------------------------------------------------------------------------
+# MINSUPPLIES <num>
+#
+# Give the number of power supplies that must be receiving power to keep
+# this system running. Most systems have one power supply, so you would
+# put "1" in this field.
+#
+# Large/expensive server type systems usually have more, and can run with
+# a few missing. Some of these can run with 2 out of 4, for example,
+# so you'd set that to 2. The idea is to keep the box running as long
+# as possible, right?
+#
+# Obviously you have to put the redundant supplies on different UPS circuits
+# for this to make sense! See big-servers.txt in the docs subdirectory
+# for more information and ideas on how to use this feature.
+
+MINSUPPLIES 1
+
+# --------------------------------------------------------------------------
+# SHUTDOWNCMD "<command>"
+#
+# upsmon runs this command when the system needs to be brought down.
+#
+# This should work just about everywhere ... if it doesn't, well, change it,
+# perhaps to a more complicated custom script.
+#
+# Note that while you experiment with the initial setup and want to test how
+# your configuration reacts to power state changes and ultimately when power
+# is reported to go critical, but do not want your system to actually turn
+# off, consider setting the SHUTDOWNCMD temporarily to do something benign -
+# such as posting a message with 'logger' or 'wall' or 'mailx'. Do be careful
+# to plug the UPS back into the wall in a timely fashion.
+
+SHUTDOWNCMD "/sbin/shutdown -h +0"
+
+# --------------------------------------------------------------------------
+# NOTIFYCMD <command>
+#
+# upsmon calls this to send messages when things happen
+#
+# This command is called with the full text of the message (from NOTIFYMSG)
+# as one argument.
+#
+# The environment string NOTIFYTYPE will contain the type string of
+# whatever caused this event to happen.
+#
+# The environment string UPSNAME will contain the name of the system/device
+# that generated the change.
+#
+# Note that this is only called for NOTIFY events that have EXEC set with
+# NOTIFYFLAG. See NOTIFYFLAG below for more details.
+#
+# Making this some sort of shell script might not be a bad idea.
+# Alternately you can use the upssched program as your NOTIFYCMD for some
+# more complex setups (e.g. to ease handling of notification storms).
+# For more information and ideas, see docs/scheduling.txt
+#
+# Example:
+# NOTIFYCMD /bin/notifyme
+
+# --------------------------------------------------------------------------
+# POLLFREQ <n>
+#
+# Polling frequency for normal activities, measured in seconds.
+#
+# Adjust this to keep upsmon from flooding your network, but don't make
+# it too high or it may miss certain short-lived power events.
+
+POLLFREQ 5
+
+# --------------------------------------------------------------------------
+# POLLFREQALERT <n>
+#
+# Polling frequency in seconds while UPS on battery.
+#
+# You can make this number lower than POLLFREQ, which will make updates
+# faster when any UPS is running on battery. This is a good way to tune
+# network load if you have a lot of these things running.
+#
+# The default is 5 seconds for both this and POLLFREQ.
+
+POLLFREQALERT 5
+
+# --------------------------------------------------------------------------
+# HOSTSYNC - How long upsmon will wait before giving up on another upsmon
+#
+# The primary upsmon process uses this number when waiting for secondary
+# systems to disconnect once it has set the forced shutdown (FSD) flag.
+# If they don't disconnect after this many seconds, it goes on without them.
+#
+# Similarly, upsmon secondary processes wait up to this interval for the
+# primary upsmon to set FSD when an UPS they are monitoring goes critical -
+# that is, on battery and low battery. If the primary doesn't do its job,
+# the secondaries will shut down anyway to avoid damage to the file systems.
+#
+# This "wait for FSD" is done to avoid races where the status changes
+# to critical and back between polls by the primary.
+
+HOSTSYNC 15
+
+# --------------------------------------------------------------------------
+# DEADTIME - Interval to wait before declaring a stale ups "dead"
+#
+# upsmon requires a UPS to provide status information every few seconds
+# (see POLLFREQ and POLLFREQALERT) to keep things updated. If the status
+# fetch fails, the UPS is marked stale. If it stays stale for more than
+# DEADTIME seconds, the UPS is marked dead.
+#
+# A dead UPS that was last known to be on battery is assumed to have gone
+# to a low battery condition. This may force a shutdown if it is providing
+# a critical amount of power to your system.
+#
+# Note: DEADTIME should be a multiple of POLLFREQ and POLLFREQALERT.
+# Otherwise you'll have "dead" UPSes simply because upsmon isn't polling
+# them quickly enough. Rule of thumb: take the larger of the two
+# POLLFREQ values, and multiply by 3.
+
+DEADTIME 15
+
+# --------------------------------------------------------------------------
+# POWERDOWNFLAG - Flag file for forcing UPS shutdown on the primary system
+#
+# upsmon will create a file with this name in primary mode when it's time
+# to shut down the load. You should check for this file's existence in
+# your shutdown scripts and run 'upsdrvctl shutdown' if it exists, to tell
+# the UPS(es) to power off.
+#
+# See the config-notes.txt file in the docs subdirectory for more information.
+# Refer to the section:
+# [[UPS_shutdown]] "Configuring automatic shutdowns for low battery events"
+# or refer to the online version.
+
+POWERDOWNFLAG /etc/killpower
+
+# --------------------------------------------------------------------------
+# NOTIFYMSG - change messages sent by upsmon when certain events occur
+#
+# You can change the default messages to something else if you like.
+#
+# NOTIFYMSG <notify type> "message"
+#
+# NOTIFYMSG ONLINE "UPS %s on line power"
+# NOTIFYMSG ONBATT "UPS %s on battery"
+# NOTIFYMSG LOWBATT "UPS %s battery is low"
+# NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
+# NOTIFYMSG COMMOK "Communications with UPS %s established"
+# NOTIFYMSG COMMBAD "Communications with UPS %s lost"
+# NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding"
+# NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced"
+# NOTIFYMSG NOCOMM "UPS %s is unavailable"
+# NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible"
+#
+# Note that %s is replaced with the identifier of the UPS in question.
+#
+# Possible values for <notify type>:
+#
+# ONLINE : UPS is back online
+# ONBATT : UPS is on battery
+# LOWBATT : UPS has a low battery (if also on battery, it's "critical")
+# FSD : UPS is being shutdown by the primary (FSD = "Forced Shutdown")
+# COMMOK : Communications established with the UPS
+# COMMBAD : Communications lost to the UPS
+# SHUTDOWN : The system is being shutdown
+# REPLBATT : The UPS battery is bad and needs to be replaced
+# NOCOMM : A UPS is unavailable (can't be contacted for monitoring)
+# NOPARENT : The process that shuts down the system has died (shutdown impossible)
+
+# --------------------------------------------------------------------------
+# NOTIFYFLAG - change behavior of upsmon when NOTIFY events occur
+#
+# By default, upsmon sends walls (global messages to all logged in users)
+# and writes to the syslog when things happen. You can change this.
+#
+# NOTIFYFLAG <notify type> <flag>[+<flag>][+<flag>] ...
+#
+# NOTIFYFLAG ONLINE SYSLOG+WALL
+# NOTIFYFLAG ONBATT SYSLOG+WALL
+# NOTIFYFLAG LOWBATT SYSLOG+WALL
+# NOTIFYFLAG FSD SYSLOG+WALL
+# NOTIFYFLAG COMMOK SYSLOG+WALL
+# NOTIFYFLAG COMMBAD SYSLOG+WALL
+# NOTIFYFLAG SHUTDOWN SYSLOG+WALL
+# NOTIFYFLAG REPLBATT SYSLOG+WALL
+# NOTIFYFLAG NOCOMM SYSLOG+WALL
+# NOTIFYFLAG NOPARENT SYSLOG+WALL
+#
+# Possible values for the flags:
+#
+# SYSLOG - Write the message in the syslog
+# WALL - Write the message to all users on the system
+# EXEC - Execute NOTIFYCMD (see above) with the message
+# IGNORE - Don't do anything
+#
+# If you use IGNORE, don't use any other flags on the same line.
+
+# --------------------------------------------------------------------------
+# RBWARNTIME - replace battery warning time in seconds
+#
+# upsmon will normally warn you about a battery that needs to be replaced
+# every 43200 seconds, which is 12 hours. It does this by triggering a
+# NOTIFY_REPLBATT which is then handled by the usual notify structure
+# you've defined above.
+#
+# If this number is not to your liking, override it here.
+
+RBWARNTIME 43200
+
+# --------------------------------------------------------------------------
+# NOCOMMWARNTIME - no communications warning time in seconds
+#
+# upsmon will let you know through the usual notify system if it can't
+# talk to any of the UPS entries that are defined in this file. It will
+# trigger a NOTIFY_NOCOMM by default every 300 seconds unless you
+# change the interval with this directive.
+
+NOCOMMWARNTIME 300
+
+# --------------------------------------------------------------------------
+# FINALDELAY - last sleep interval before shutting down the system
+#
+# On a primary, upsmon will wait this long after sending the NOTIFY_SHUTDOWN
+# before executing your SHUTDOWNCMD. If you need to do something in between
+# those events, increase this number. Remember, at this point your UPS is
+# almost depleted, so don't make this too high. If needed, on high-end UPS
+# devices you can usually configure when the low-battery state is announced
+# based on estimated remaining run-time or on charge level of the batteries.
+#
+# Alternatively, you can set this very low so you don't wait around when
+# it's time to shut down. Some UPSes don't give much warning for low
+# battery and will require a value of 0 here for a safe shutdown.
+#
+# Note: If FINALDELAY on the secondary is greater than HOSTSYNC on the
+# primary, the primary will give up waiting for that secondary system
+# to disconnect.
+
+FINALDELAY 5
+
+# --------------------------------------------------------------------------
+# CERTPATH - path to certificates (database directory or directory with CA's)
+#
+# When compiled with SSL support, you can enter the certificate path here.
+#
+# With NSS:
+# Certificates are stored in a dedicated database (split into 3 files).
+# Specify the path of the database directory.
+#
+# CERTPATH /etc/nut/cert/upsmon
+#
+# With OpenSSL:
+# Directory containing CA certificates in PEM format, used to verify
+# the server certificate presented by the upsd server. The files each
+# contain one CA certificate. The files are looked up by the CA subject
+# name hash value, which must hence be available.
+#
+# CERTPATH /usr/ssl/certs
+#
+# See 'docs/security.txt' or the Security chapter of NUT user manual
+# for more information on the SSL support in NUT.
+
+# --------------------------------------------------------------------------
+# CERTIDENT - self certificate name and database password
+# CERTIDENT <certificate name> <database password>
+#
+# When compiled with SSL support with NSS, you can specify the certificate
+# name to retrieve from database to authenticate itself and the password
+# required to access certificate related private key.
+#
+# CERTIDENT "my nut monitor" "MyPasSw0rD"
+#
+# See 'docs/security.txt' or the Security chapter of NUT user manual
+# for more information on the SSL support in NUT.
+
+# --------------------------------------------------------------------------
+# CERTHOST - security properties for an host
+# CERTHOST <hostname> <certificate name> <certverify> <forcessl>
+#
+# When compiled with SSL support with NSS, you can specify security directive
+# for each server you can contact.
+# Each entry maps server name with the expected certificate name and flags
+# indicating if the server certificate is verified and if the connection
+# must be secure.
+#
+# CERTHOST localhost "My nut server" 1 1
+#
+# See 'docs/security.txt' or the Security chapter of NUT user manual
+# for more information on the SSL support in NUT.
+
+# --------------------------------------------------------------------------
+# CERTVERIFY - make upsmon verify all connections with certificates
+# CERTVERIFY 1
+#
+# When compiled with SSL support, make upsmon verify all connections with
+# certificates.
+# Without this, there is no guarantee that the upsd is the right host.
+# Enabling this greatly reduces the risk of man in the middle attacks.
+# This effectively forces the use of SSL, so don't use this unless
+# all of your upsd hosts are ready for SSL and have their certificates
+# in order.
+# When compiled with NSS support of SSL, can be overridden for host
+# specified with a CERTHOST directive.
+
+
+# --------------------------------------------------------------------------
+# FORCESSL - force upsmon to use SSL
+# FORCESSL 1
+#
+# When compiled with SSL, specify that a secured connection must be used
+# to communicate with upsd.
+# If you don't use 'CERTVERIFY 1', then this will at least make sure
+# that nobody can sniff your sessions without a large effort. Setting
+# this will make upsmon drop connections if the remote upsd doesn't
+# support SSL, so don't use it unless all of them have it running.
+# When compiled with NSS support of SSL, can be overridden for host
+# specified with a CERTHOST directive.
+
+# --------------------------------------------------------------------------
+# DEBUG_MIN - specify minimal debugging level for upsmon daemon
+# e.g. DEBUG_MIN 6
+#
+# Optionally specify a minimum debug level for `upsmon` daemon, e.g. for
+# troubleshooting a deployment, without impacting foreground or background
+# running mode directly, and without need to edit init-scripts or service
+# unit definitions. Note that command-line option `-D` can only increase
+# this verbosity level.
+#
+# NOTE: if the running daemon receives a `reload` command, presence of the
+# `DEBUG_MIN NUMBER` value in the configuration file can be used to tune
+# debugging verbosity in the running service daemon (it is recommended to
+# comment it away or set the minimum to explicit zero when done, to avoid
+# huge journals and I/O system abuse). Keep in mind that for this run-time
+# tuning, the `DEBUG_MIN` value *present* in *reloaded* configuration files
+# is applied instantly and overrides any previously set value, from file
+# or CLI options, regardless of older logging level being higher or lower
+# than the newly found number; a missing (or commented away) value however
+# does not change the previously active logging verbosity.
+#